Skip to main content
Smart PV Controller

Smart PV Controller

The SUN2000 is a three-phase grid-tied PV string inverter that converts the DC power generated by PV strings into AC power and feeds the power to the power grid.

The SUN2000 applies to grid-tied PV systems for commercial rooftops and large PV plants. Typically, a grid-tied PV system consists of the PV string, SUN2000, alternating current distribution unit (ACDU), and isolation transformer.

  • Product Description

    Function

    The SUN2000 is a three-phase grid-tied PV string inverter that converts the DC power generated by PV strings into AC power and feeds the power to the power grid.

    Models

    Figure 2-1 Designation explanation of the SUN2000-60KTL-M0
    download?uuid=08f3ce93bd584f8cbe221180bc661cdc

    Model

    Rated Output Power

    Rated Output Voltage

    SUN2000-50KTL-M0

    50 kW

    380 V/400 V/415 V

    SUN2000-60KTL-M0

    60 kW

    380 V/400 V/480 V

    SUN2000-65KTL-M0

    65 kW

    480 V

    Networking Application

    The SUN2000 applies to grid-tied PV systems for commercial rooftops and large PV plants. Typically, a grid-tied PV system consists of the PV string, SUN2000, alternating current distribution unit (ACDU), and isolation transformer.

  • Product Technical Details

    Efficiency

    Item

    SUN2000-50KTL-M0

    SUN2000-60KTL-M0

    SUN2000-65KTL-M0

    Maximum efficiency

    98.70%

    98.70% (380 V/400 V)

    98.90% (480 V)

    98.90%

    European efficiency

    98.50%

    98.50% (380 V/400 V)

    98.70% (480 V)

    98.70%

    Input

    Item

    SUN2000-50KTL-M0

    SUN2000-60KTL-M0

    SUN2000-65KTL-M0

    Maximum input power

    56,200 W

    67,400 W

    73,500 W

    Maximum input voltagea

    1100 V

    Operating voltage rangeb

    200–1000 V

    Maximum input current (per MPPT)

    22 A

    Maximum short-circuit current (per MPPT)

    30 A

    Maximum SUN2000 backfeed current to the PV array

    0 A

    Minimum startup voltage

    200 V

    Full power MPPT voltage range

    520–800 V

    520–800 V (380 V/400 V), 600–850 V (480 V)

    600–850 V

    Rated input voltage

    600 V (380 V/400 V), 620 V (415 V)

    600 V (380 V/400 V), 720 V (480 V)

    720 V

    Number of inputs

    12

    Number of MPP trackers

    6

    Note a: The maximum input voltage is the upper threshold of the DC voltage. If the input voltage exceeds the threshold, the solar inverter may be damaged.

    Note b: If the input voltage is beyond the operating voltage range, the solar inverter cannot work properly.

    Output

    Item

    SUN2000-50KTL-M0

    SUN2000-60KTL-M0

    SUN2000-65KTL-M0

    Rated active power

    50 kW

    60 kW

    65 kW

    Maximum apparent power

    55 kVA

    66 kVA

    72 kVA

    Maximum active power (cosφ = 1)

    55 kW (Can be set to 50 kW)

    66 kW (Can be set to 60 kW)

    72 kW

    Rated output voltagea

    220 V/380 V, 230 V/400 V, 240 V/415 V, 3W+(N)b+PE

    220 V/380 V, 230 V/400 V, 277 V/480 V, 3W+(N)b+PE

    277 V/480 V, 3W+PE

    Rated output current

    76 A (380 V), 72.2 A (400 V), 69.6 A (415 V)

    91.2 A (380 V) 86.7 A (400 V), 72.2 A (480 V)

    78.2 A

    Adapted grid frequency

    50 Hz/60 Hz

    Maximum output current

    83.6 A (380 V), 79.4 A (400 V), 76.6 A (415 V)

    100 A (380 V), 95.3 A (400 V), 79.4 A (480 V)

    86.7 A

    Power factor

    0.8 leading … 0.8 lagging

    Maximum total harmonic distortion (rated power)

    < 3%

    Note a: The rated output voltage is determined by Grid code, which can be set on the SUN2000 app, SmartLogger, or NetEco.

    Note b: Choose whether to connect the neutral wire to the SUN2000-50KTL-M0 and SUN2000-60KTL-M0 based on the application scenario. When it is used in the scenarios without neutral wires, set Output mode to Three-phase, three-wire. When it is used in the scenarios with neutral wires, set Output mode to Three-phase, four-wire.

  • Features

    Smart

    • Smart I-V Curve Diagnosis supported

    Efficient

    • Max. efficiency 98.7%

    Safe

    • Fuse free design

    Reliable

    • Type II surge arresters for DC & AC