Solar Energy
Smart PV Controller
The SUN2000 is a three-phase grid-tied PV string inverter that converts the DC power generated by PV strings into AC power and feeds the power to the power grid.
The SUN2000 applies to grid-tied PV systems for commercial rooftops and large PV plants. Typically, a grid-tied PV system consists of the PV string, SUN2000, alternating current distribution unit (ACDU), and isolation transformer.
Product Description
Function
The SUN2000 is a three-phase grid-tied PV string inverter that converts the DC power generated by PV strings into AC power and feeds the power to the power grid.
Models
Model |
Rated Output Power |
Rated Output Voltage |
---|---|---|
SUN2000-50KTL-M0 |
50 kW |
380 V/400 V/415 V |
SUN2000-60KTL-M0 |
60 kW |
380 V/400 V/480 V |
SUN2000-65KTL-M0 |
65 kW |
480 V |
Networking Application
The SUN2000 applies to grid-tied PV systems for commercial rooftops and large PV plants. Typically, a grid-tied PV system consists of the PV string, SUN2000, alternating current distribution unit (ACDU), and isolation transformer.
Product Technical Details
Efficiency
Item |
SUN2000-50KTL-M0 |
SUN2000-60KTL-M0 |
SUN2000-65KTL-M0 |
|
---|---|---|---|---|
Maximum efficiency |
98.70% |
98.70% (380 V/400 V) |
98.90% (480 V) |
98.90% |
European efficiency |
98.50% |
98.50% (380 V/400 V) |
98.70% (480 V) |
98.70% |
Input
Item |
SUN2000-50KTL-M0 |
SUN2000-60KTL-M0 |
SUN2000-65KTL-M0 |
---|---|---|---|
Maximum input power |
56,200 W |
67,400 W |
73,500 W |
Maximum input voltagea |
1100 V |
||
Operating voltage rangeb |
200–1000 V |
||
Maximum input current (per MPPT) |
22 A |
||
Maximum short-circuit current (per MPPT) |
30 A |
||
Maximum SUN2000 backfeed current to the PV array |
0 A |
||
Minimum startup voltage |
200 V |
||
Full power MPPT voltage range |
520–800 V |
520–800 V (380 V/400 V), 600–850 V (480 V) |
600–850 V |
Rated input voltage |
600 V (380 V/400 V), 620 V (415 V) |
600 V (380 V/400 V), 720 V (480 V) |
720 V |
Number of inputs |
12 |
||
Number of MPP trackers |
6 |
||
Note a: The maximum input voltage is the upper threshold of the DC voltage. If the input voltage exceeds the threshold, the solar inverter may be damaged. Note b: If the input voltage is beyond the operating voltage range, the solar inverter cannot work properly. |
Output
Item |
SUN2000-50KTL-M0 |
SUN2000-60KTL-M0 |
SUN2000-65KTL-M0 |
---|---|---|---|
Rated active power |
50 kW |
60 kW |
65 kW |
Maximum apparent power |
55 kVA |
66 kVA |
72 kVA |
Maximum active power (cosφ = 1) |
55 kW (Can be set to 50 kW) |
66 kW (Can be set to 60 kW) |
72 kW |
Rated output voltagea |
220 V/380 V, 230 V/400 V, 240 V/415 V, 3W+(N)b+PE |
220 V/380 V, 230 V/400 V, 277 V/480 V, 3W+(N)b+PE |
277 V/480 V, 3W+PE |
Rated output current |
76 A (380 V), 72.2 A (400 V), 69.6 A (415 V) |
91.2 A (380 V) 86.7 A (400 V), 72.2 A (480 V) |
78.2 A |
Adapted grid frequency |
50 Hz/60 Hz |
||
Maximum output current |
83.6 A (380 V), 79.4 A (400 V), 76.6 A (415 V) |
100 A (380 V), 95.3 A (400 V), 79.4 A (480 V) |
86.7 A |
Power factor |
0.8 leading … 0.8 lagging |
||
Maximum total harmonic distortion (rated power) |
< 3% |
||
Note a: The rated output voltage is determined by Grid code, which can be set on the SUN2000 app, SmartLogger, or NetEco. Note b: Choose whether to connect the neutral wire to the SUN2000-50KTL-M0 and SUN2000-60KTL-M0 based on the application scenario. When it is used in the scenarios without neutral wires, set Output mode to Three-phase, three-wire. When it is used in the scenarios with neutral wires, set Output mode to Three-phase, four-wire. |
Features
Smart
- Smart I-V Curve Diagnosis supported
Efficient
- Max. efficiency 98.7%
Safe
- Fuse free design
Reliable
- Type II surge arresters for DC & AC